INSTALLATION OF VENTING SYSTEM COMPONENTS WARNING Refer to the LAARS EVERHOT® IGI series Water Heater Installation and Operating In
10 NOTICE Note: 3.5” (90 mm) is the minimum outer cap length. If needed the length outside the wall may exceed this dimension. Final installat
11Horizontal Vent System Installation examples Figure 36
12Installation Instructions Everhot Vertical Discharge Vent System Figure 37 Identify the vent location Determine the location where the roof dis
13Mounting the vent system Figure 39 Vent connections must be firmly pressed together so that the gaskets form an airtightseal. Secure the system
14Vertical Vent System Installation examples Figure 40
15Cut Line Template
800.900.9276 • Fax 800.559.1583 (Customer Service, Service Advisors)20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355 (Applicat
2 WARNING All joints in the vent/air intake piping must be taped with aluminum tape at the completion of the venting system installation to prevent a
3 * For clearances not specified in ANSI Z223.1 / NFP A 54 or CGA-B149, please use clearances in accordance with local installation codes and the
4 General Installation Instructions Joint connection Figure 13 Vent connections others must be firmly pressed together so that the gaskets form a
5Condensate drain Every vent system should have a condensate collector unless installed with a total vent length of less than 5 ft. (1,52 m).
6 Parts & Dimensions Components needed for direct vent applications: Figure 19 Figure 20 1) horizontal discharge adapter 2) vertical di
7 Figure 23 Figure 24 Figure 25 5) vent extension 6) 45º vent pipe elbow 7) 90 º vent pipe elbow 10” BWC p/n 239-44496-00
8 Figure 30 Figure 31 12) flat roof flashing 13) condensate trap kit BWC p/n 239-44492-00
9Installation Instructions Everhot Horizontal Discharge Vent System Identify the vent location Figure 32 Steps: - Place horizontal discharge adap