Modulating and Condensing /
Non-condensing Boiler control
M4-LHS
Hybrid Multi-Boiler Control
HTC# 059295-00 A
WARNING
FOR YOUR SAFETY: This product must be installed and serviced by
a professional service technician, qualified in hot water heater/boiler
controls installation and maintenance. This manual is intended for
anyone who will install, operate or maintain the control system. Before
you begin installation and operation of this control, it is important that
you thoroughly review this manual. Improper installation and operation
could result in damage to equipment and possibly even personal
injury. Laars Controls are not intended for use as operation safety limit
controls. Another control, that is intended and certified as a high limit
control, must be in the water heater/boiler control circuit.
Installation and Operation Manual
Page view 0
1 2 3 4 5 6 ... 54 55

Summary of Contents

Page 1 - Hybrid Multi-Boiler Control

Document 4232Modulating and Condensing / Non-condensing Boiler controlM4-LHSHybrid Multi-Boiler ControlHTC# 059295-00 A WARNINGFOR YOUR SAFETY: This

Page 2 - Contents

HT# 059295-00 A10 M4-LHS Installation and Operation Manual INSTALLATIONEach of the M4-LHS or Extension consists of three primary enclosure component

Page 3 - HYBRID LOGIC OVERVIEW

HT# 059295-00 AM4-LHS Installation and Operation Manual 11INSTALL THE SENSORSSystem Sensor Installation• Only use the System sensor (CA002500 or eq

Page 4 - MODULATING LOGIC OVERVIEW

HT# 059295-00 A12 M4-LHS Installation and Operation Manual WIRING• All wiring must enter the enclosure through the bottom knockouts.• Class 1 vo

Page 5 - OUTDOOR RESET CONCEPT

HT# 059295-00 AM4-LHS Installation and Operation Manual 13• When the Shutdown input is enabled by closing the dry contact, or when the Tstat input

Page 6 - CONTROL LAYOUT

HT# 059295-00 A14 M4-LHS Installation and Operation Manual Wiring the Boilers• When wiring Condensing and Non-Condensing boilers make sure that th

Page 7 - EXTENSION LAYOUT

HT# 059295-00 AM4-LHS Installation and Operation Manual 15Connecting to the Extensions and 4-20mA EMS Interface ALERTTo set the Extension to a specif

Page 8 - FEATURES

HT# 059295-00 A16 M4-LHS Installation and Operation Manual Connecting to BACnet Interface Module• The M4-LHS can communicate to BACnet MSTP networ

Page 9

HT# 059295-00 AM4-LHS Installation and Operation Manual 17-------- SETTINGS ---- Season Winter System Target 140oF <System Settings> <Maint

Page 10 - INSTALLATION

HT# 059295-00 A18 M4-LHS Installation and Operation Manual - EMS INPUT MODE -Disable EnableBACK ▲ ▼ SAVE-EMS 4ma SETPOINT -70 oF[ ]BAC

Page 11 - INSTALL THE SENSORS

HT# 059295-00 AM4-LHS Installation and Operation Manual 19STARTUP SETTINGSProgram Change Switch SettingTo be able to change the M4-LHS settings the P

Page 12 - HYBRID CONTROL

HT# 059295-00 A2 M4-LHS Installation and Operation Manual Hybrid Logic Overview . . . . . . . . . . . . . . . . . . 3Modulating Lo

Page 13 - Wiring the System Output

HT# 059295-00 A20 M4-LHS Installation and Operation Manual EMS 4mA and 20mA Set Points4mA: can be set from 50°F/ 10°C to 200°F/93°C Default: 70°F/

Page 14 - Boiler Type)

HT# 059295-00 AM4-LHS Installation and Operation Manual 21Switch DelayAdjustablefrom0.0to12.0Hours Default:0.5hoursButton: MENU/<System St

Page 15

HT# 059295-00 A22 M4-LHS Installation and Operation Manual HYBRID MODULATING BOILER SETTINGSModulating Output Type4-20mA,0-10V,1-10V(Custom)Outp

Page 16 - ACTIVATE THE BATTERY

HT# 059295-00 AM4-LHS Installation and Operation Manual 23MODULATING BOILER SETTINGSBoiler NumberAdjustablefrom1to15 Default:1Button: MENU/<

Page 17

HT# 059295-00 A24 M4-LHS Installation and Operation Manual STARTUP SETTINGS (CONTINUED)Prove/Indirect Domestic Hot Water (DHW) PriorityProve,DHWPr

Page 18

HT# 059295-00 AM4-LHS Installation and Operation Manual 25Boost Mode(Not Available in Setback Mode)30Minutes,Disabled Default:DisableButton: MEN

Page 19

HT# 059295-00 A26 M4-LHS Installation and Operation Manual BACNET MSTP COMMUNICATION MENU-------- SETTINGS ---- Season Winter System Target 140oF &

Page 20 - HYBRID STARTUP SETTINGS

HT# 059295-00 AM4-LHS Installation and Operation Manual 27OPERATING SETTINGSProgram Change Switch SettingTo be able to change the M4-LHS settings, th

Page 21 - HT# 059295-00 A

HT# 059295-00 A28 M4-LHS Installation and Operation Manual ALERTTo be able to change the M4-LHS settings the Program/Run Switch must be set to Prog

Page 22 - WARNING

HT# 059295-00 AM4-LHS Installation and Operation Manual 29 ALERTTo be able to change the M4-LHS settings the Program/Run Switch must be set to Progra

Page 23 - MODULATING BOILER SETTINGS

HT# 059295-00 AM4-LHS Installation and Operation Manual 3HYBRID LOGIC OVERVIEWIn response to new advancement in condensing boiler design and size, ma

Page 24 - STARTUP SETTINGS (CONTINUED)

HT# 059295-00 A30 M4-LHS Installation and Operation Manual OffsetAdjustablefrom50Fº/28Cºto-50Fº/-28Cº Default:0Fº/0CºButton: MENU/System Targ

Page 25 - Sensor Fault

HT# 059295-00 AM4-LHS Installation and Operation Manual 31SYSTEM SETTINGSButton: MENU/<System Settings>Settings 1 and Settings 2 menus pr

Page 26

HT# 059295-00 A32 M4-LHS Installation and Operation Manual • The System Run-On time should be set based on the size and type of the boilers and pu

Page 27

HT# 059295-00 AM4-LHS Installation and Operation Manual 33MODULATING BOILER OPERATING SETTINGSGainAdjustablefrom-10to+10 Default:0Button: MENU/

Page 28

HT# 059295-00 A34 M4-LHS Installation and Operation Manual STAGING BOILER OPERATING SETTINGSReaction TimeAdjustablefrom1to10minutes Default:

Page 29

HT# 059295-00 AM4-LHS Installation and Operation Manual 35Avoiding Conicting Boiler LimitsThe temperature limits set on the boilers MUST be set cons

Page 30 - Target Offset

HT# 059295-00 A36 M4-LHS Installation and Operation Manual DAY - NIGHT SCHEDULE(Available when "Shutdown or Tstat" is selected from the Sh

Page 31 - SYSTEM SETTINGS

HT# 059295-00 AM4-LHS Installation and Operation Manual 37Output Modulation Trim(Available for modulating boilers only)Adjustablefrom-1.0to+1.0

Page 32

HT# 059295-00 A38 M4-LHS Installation and Operation Manual BOILER STATUSThe M4-LHS boiler status gives immediate access to each boiler stages or mod

Page 33

HT# 059295-00 AM4-LHS Installation and Operation Manual 39OD= 55oF SYS=143oF <<A>> B 67% 20%STAGE ◄ ► MENUSTAGE A SETTINGSMode Auto &

Page 34

HT# 059295-00 A4 M4-LHS Installation and Operation Manual MODULATING LOGIC OVERVIEWThe Modulation PID logic is capable of controlling multiple modul

Page 35

HT# 059295-00 A40 M4-LHS Installation and Operation Manual Auto The M4-LHS will control the boiler’s operation to maintain the desired Set Point.

Page 36 - MAINTENANCE

HT# 059295-00 AM4-LHS Installation and Operation Manual 41TROUBLESHOOTINGSENSOR INPUTSDisplay shows Sensor OPEN or SHORT When the display shows sen

Page 37 - Conguration

HT# 059295-00 A42 M4-LHS Installation and Operation Manual Too Little Heat• ResetRatioandOffset- If reduced heat occurs only in certain weathe

Page 38 - BOILER STAGE MENU

HT# 059295-00 AM4-LHS Installation and Operation Manual 43SPECIFICATIONSVoltageInput: . . . . . . . . . . . . . . . . . . . .

Page 39

HT# 059295-00 A44 M4-LHS Installation and Operation Manual HYBRID - OUTDOOR RESET - BACNET VARIABLE LISTHybrid Object ID Object Type Object Value Ob

Page 40

HT# 059295-00 AM4-LHS Installation and Operation Manual 45MODULATION - OUTDOOR RESET - BACNET VARIABLE LISTHybrid Object ID Object Type Object Value

Page 41 - TROUBLESHOOTING

HT# 059295-00 A46 M4-LHS Installation and Operation Manual MODULATION - SET POINT - BACNET VARIABLE LISTHybrid Object ID Object Type Object Value Ob

Page 42

HT# 059295-00 AM4-LHS Installation and Operation Manual 47BACNET PICS STATEMENTProduct Model Number Protocol Revision Software Version Firmware Vers

Page 43 - EXTENSION SPECIFICATIONS

HT# 059295-00 A48 M4-LHS Installation and Operation Manual SYSTEMABCD12RUNPROGRAMDO NOT APPLY ANY VOLTAGETO INPUT TERMINALS3456789101112131514171618

Page 44

HT# 059295-00 AM4-LHS Installation and Operation Manual 49Boiler 1Boiler 2Boiler 3Boiler 4Boiler 1Boiler 24 - 20 mAModulatingSignal OutputsOutdoor Se

Page 45

HT# 059295-00 AM4-LHS Installation and Operation Manual 5OUTDOOR RESET CONCEPTThe M4-LHS has multiple operating modes that satisfy most hydronic syst

Page 46

HT# 059295-00 A50 M4-LHS Installation and Operation Manual SYSTEMABCD12RUNPROGRAMDO NOT APPLY ANY VOLTAGETO INPUT TERMINALS3456789101112131514171618

Page 47 - BACNET PICS STATEMENT

HT# 059295-00 A48 M4-LHS Installation and Operation Manual SYSTEMABCD12RUNPROGRAMDO NOT APPLY ANY VOLTAGETO INPUT TERMINALS3456789101112131514171618

Page 48 - PIPING AND WIRING DIAGRAMS

HT# 059295-00 AM4-LHS Installation and Operation Manual 49Boiler 1Boiler 2Boiler 3Boiler 4Boiler 1Boiler 24 - 20 mAModulatingSignal OutputsOutdoor Se

Page 49 - HYBRID WIRING DIAGRAM

HT# 059295-00 A50 M4-LHS Installation and Operation Manual SYSTEMABCD12RUNPROGRAMDO NOT APPLY ANY VOLTAGETO INPUT TERMINALS3456789101112131514171618

Page 50 - MODULATING PIPING DIAGRAM

HT# 059295-00 AM4-LHS Installation and Operation Manual 51Boiler 3Boiler 4Boiler 1Boiler 2Boiler 3Boiler 4Boiler 1Boiler 24 - 20 mAModulatingSignal O

Page 51

20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • FAX 603.335.33551355 Kuehner Drive, Simi Valley, CA 93063 • 800.900.9267 • FAX 800.559.1583 (S

Page 52

HT# 059295-00 A6 M4-LHS Installation and Operation Manual PART NUMBER # CA00920012RUNPROGRAMDO NOT APPLY ANY VOLTAGETO INPUT TERMINALS34567891011121

Page 53

HT# 059295-00 AM4-LHS Installation and Operation Manual 7PART NUMBER # CA004400Ext AM4ExtFULL MODULATION SEQUENCING EXTENSIONFHJPowerEGICommKMOLNPCAU

Page 54 - MODULATING WIRING DIAGRAM

HT# 059295-00 A8 M4-LHS Installation and Operation Manual FEATURESLaars designed the M4-LHS with Hydronic building heating, using both condensing an

Page 55 - HTC# 059295-00 A

HT# 059295-00 AM4-LHS Installation and Operation Manual 9Setback or Day/Night SchedulingTwo Setback modes are available for the M4-LHS:• The Day/Ni