Installation and Operation Instructions Document 1065D
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualified in hot water heater installation and maintenance. Improper installation and/or operation could
create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death.
Improper installation and/or operation will void the warranty.
WARNING
If the information in this manual is not followed exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or
any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a nearby phone. Follow the gas supplier's
instructions.
If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or gas
supplier.
Installation and Operation
Instructions for
Mighty Therm
Model HH
Sizes 2000-5000
Hydronic Boilers
A subsidiary of BRADFORD WHITE Corporation
Page view 0
1 2 3 4 5 6 ... 23 24

Summary of Contents

Page 1 - Mighty Therm

H0147600DInstallation and Operation Instructions Document 1065DFOR YOUR SAFETY: This product must be installed and serviced by a professional service

Page 2 - TABLE OF CONTENTS

LAARS Heating SystemsPage 102H. Filling Fully-Connected System1. Close all bleeding devices and open make-upwater valve. Allow system to fill slowly.2

Page 3 - General Information

Mighty Therm Hydronic BoilerPage 113. Once the pilots are lit and have been establishedfor five minutes, the flame failure response timeshould be chec

Page 4 - 1B. Flow Requirements

LAARS Heating SystemsPage 12Top ViewView On Arrow ABurnerC/L 4th PortAObservation HoleBurner3C. To Turn Off Boiler1. Turn off main electrical switch.2

Page 5 - Installation

Mighty Therm Hydronic BoilerPage 13With a wire brush, remove soot and loose scalefrom the heat exchanger. Do not use water orcompressed air for cleani

Page 6

LAARS Heating SystemsPage 144. Boiler is pounding, Knocking or emitting steamfrom relief valves.Possible Cause What To DoA. Low or no water flow. A.Th

Page 7

Mighty Therm Hydronic BoilerPage 157. Water dripping in firebox. Possible Cause What To DoA. If boiler is use

Page 8 - 2E. Gas Supply and Piping

LAARS Heating SystemsPage 16Figure 13. Outdoor Parts Identification.

Page 9 - 2F. Electrical Wiring

Mighty Therm Hydronic BoilerPage 175. Remove outer screw from upper end panel atjunction with lower end panel.6. Remove and disconnect all probes and

Page 10 - Operation

LAARS Heating SystemsPage 18Key Size Size Size Size Size Size SizeNo. Description 2000 I 2450 I 3050 I 3500 I 4050 I 4500 I 5000 I2200 E 2800 E 3200 E

Page 11 - 3B. To Start Up System

Mighty Therm Hydronic BoilerPage 19Figure 14. Parts Identification.

Page 12 - Maintenance

LAARS Heating SystemsPage 2TABLE OF CONTENTSSECTION 1.General Information1A. Introduction... 31B. Flow

Page 13 - Service Problems

LAARS Heating SystemsPage 20Key Size Size Size Size Size Size SizeNo. Description 2000 I 2450 I 3050 I 3500 I 4050 I 4500 I 5000 I2200 E 2800 E 3200 E

Page 14 - LAARS Heating Systems

Mighty Therm Hydronic BoilerPage 21Figure 15. Tile Assembly.

Page 15 - SECTION 6

LAARS Heating SystemsPage 22Key Size Size Size Size Size Size SizeNo. Description 2000 I 2450 I 3050 I 3500 I 4050 I 4500 I 5000 I2200 E 2800 E 3200 E

Page 16

Mighty Therm Hydronic BoilerPage 23

Page 17 - Section 2 (See Figure 13)

H0147600D800.900.9276 • Fax 800.559.1583 (Customer Service, Service Advisors)20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.33551

Page 18 - SECTION 7

Mighty Therm Hydronic BoilerPage 3SECTION 1.General Information IMPORTANT WARNING:The Model HH hydronic boiler must be installed inaccordance with the

Page 19

LAARS Heating SystemsPage 41B. Flow RequirementsAll low volume hydronic boilers must havecontinuous flow through the heat exchanger whenfiring, for pr

Page 20

Mighty Therm Hydronic BoilerPage 51C-1. A Special Note About 3-WayWater Valves3-way water valves (2 position or proportional)are sometimes used to div

Page 21

LAARS Heating SystemsPage 6NOTE: In Canada (Table 3 does not apply)consult local building and safety codes or, in theabsence of such requirements, fo

Page 22

Mighty Therm Hydronic BoilerPage 7WindowOr GrillIndoorRoomWRONG5. Always use double-wall or insulated vent pipe(Type B or equivalent). In cold weather

Page 23

LAARS Heating SystemsPage 8wind conditions are possible, locate the boilerat least three (3) feet from the structures.3. Never install the boiler unde

Page 24 - H0147600D

Mighty Therm Hydronic BoilerPage 98. Before operating the boiler, the complete gassupply system and all connections must be testedfor leaks using a so