Rheos / Rheos+ Service Clearances 09-12 May 21, 2009 To: Manufacturer’s Representatives and Distributors, Contract Service Centers, Sales Team, In
Rheos+ Boiler and Water HeaterPage 9Term DescriptionPipe Single-wall galvanized steel pipe, 24 gauge minimum (sized per section 1.9)Joint Permanent
LAARS Heating SystemsPage 10*When vent terminal is less than 10 feet (3m) horizontally from a fo
Rheos+ Boiler and Water HeaterPage 111. The gure in this addendum shows the requirements for mechanical vent terminal clearances for the U.S. and Ca
LAARS Heating SystemsPage 12(c) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side w
Rheos+ Boiler and Water HeaterPage 13Model and Distance from Gas Meter or Last Stage RegulatorGas Type 0-50 feet 0-15m 50-100 feet 15-31m 100-200
LAARS Heating SystemsPage 147. All threaded joints should be coated with piping compound resistant to action of liqueed petroleum gas.8. The appl
Rheos+ Boiler and Water HeaterPage 15medium is piped in parallel with the boiler with appropriate valves to prevent the chilled medium from entering t
LAARS Heating SystemsPage 16 Water HeaterIn a water heating application (an open system), new water is constantly bei
Rheos+ Boiler and Water HeaterPage 17If the water at the inlet of the copper heat exchanger is less than 140°F (60°C), water from the outlet of the co
LAARS Heating SystemsPage 18NOTE: These systems are not allowed in the Commonwealth of Massac
Installation and Operation Instructions Document 1185B H2310800BInstallat
Rheos+ Boiler and Water HeaterPage 19Rheos+ heaters are not designed to be pl
LAARS Heating SystemsPage 20
Rheos+ Boiler and Water HeaterPage 21
LAARS Heating SystemsPage 22
Rheos+ Boiler and Water HeaterPage 23
LAARS Heating SystemsPage 24Section 5 WARNINGThe appliance must be electrically grounded in accordance with the requirements o
Rheos+ Boiler and Water HeaterPage 25temperature is less than 140°F (60°C), internal mixing will keep the outlet temperature at 160-165°F (71-74°C), a
LAARS Heating SystemsPage 26is drawing down, the heater will react to sustain a minimum tank temperature. Boilers generally have higher differential
Rheos+ Boiler and Water HeaterPage 27The proportional control used on the Rheos+ has internal circuitry that helps to minimi
LAARS Heating SystemsPage 28another 20-25°F (11-14°C) (when at high re), and it leaves the boiler at 160-165°F (71-74°C). This hot water is then s
LAARS Heating SystemsPage 2
Rheos+ Boiler and Water HeaterPage 29The second menu “Add” has to do with the N2 address. Pressing enter when “Add” is displayed will display “255”,
LAARS Heating SystemsPage 30
Rheos+ Boiler and Water HeaterPage 31
LAARS Heating SystemsPage 32
Rheos+ Boiler and Water HeaterPage 33
LAARS Heating SystemsPage 34Figure 21 - Wiring Schematic, Model 1200, Figure 22 - Wiring Schematic, Models 1600, 2000 and
Rheos+ Boiler and Water HeaterPage 35Figure 24 - Wiring Schematic, Models 1600, 2000
LAARS Heating SystemsPage 36Section 6 1. Ensure the system is fully connected. Close all bleedin
Rheos+ Boiler and Water HeaterPage 375. Remove the two plugs from the + and – ports of the
LAARS Heating SystemsPage 38 (c) Open gas shutoff valve. Restart the appliance. The ignition sequence will start again and the burner will start.
Rheos+ Boiler and Water HeaterPage 3Section 1 General Information1.1 Introduction ...
Rheos+ Boiler and Water HeaterPage 39Figure 27 - Gas Trains
LAARS Heating SystemsPage 40Figure 28 - Gas TrainsSolenoid SafetyGas ValveModulating GasValve ActuatorModulating GasValve BodiesManualGas ValveOn/Of
Rheos+ Boiler and Water HeaterPage 41shutoff valve. Remove the front and right-side panels from the unit. Disconnect the union between the valve body
LAARS Heating SystemsPage 427.2.10 Mixing ActuatorThe mixing actuator connects to both mixing valves and takes its signal from the mixing control to
Rheos+ Boiler and Water HeaterPage 438. Clean the heat exchanger: A light accumulation of soot or corrosion on the outside of the heat exchanger can
LAARS Heating SystemsPage 446. When the call for heat is complete, or the unit reaches its setpoint temperature, the gas valve will close, and the
Rheos+ Boiler and Water HeaterPage 45 Short cycling will generally occur only in combination space heating and water h
LAARS Heating SystemsPage 46 See Figure 30 1200 1600 2000 24002 Base assembly 24A1200 24A1200 24A1200 2
Rheos+ Boiler and Water HeaterPage 4750 Tubing/Fittings (gas train repair kit) R2020700 R2020700 R2020700 R202070051 Air lter box assembly (wit
LAARS Heating SystemsPage 48See Figures 34 and 35 1200 1600 2000 2400110 Header cover 12A4200 16A4200 20A4200 24
LAARS Heating SystemsPage 4Table 1 Clearances ...6Table 2 Vent / Air Pipe Sizes ...
Rheos+ Boiler and Water HeaterPage 49
LAARS Heating SystemsPage 50
Rheos+ Boiler and Water HeaterPage 513738 OR 4241(Primary)41(Secondary)42 OR 434446 OR 4749485067633738 OR4039 OR 4041
LAARS Heating SystemsPage 52
Rheos+ Boiler and Water HeaterPage 53
LAARS Heating SystemsPage 54
Rheos+ Boiler and Water HeaterPage 55
Page 56H2310800B®800.900.9276 • Fax 800.559.1583 (Customer Service, Service Advisors)20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.
Rheos+ Boiler and Water HeaterPage 5Section 1GENERAL INFORMATIONUSING THIS MANUAL – Because the Rheos+ Boilers and Rheos+ Water Heaters are identical
LAARS Heating SystemsPage 6(12) Firing Mode F = Modulating(13) Revision 2 = Second version(14) Heat Exchanger E = Glass-lined steel with copper t
Rheos+ Boiler and Water HeaterPage 7Figure 1 - Dimensional DrawingModel Intake Exhaust Intake Exhaust Size Size Maximum Run Maximum Run 1200
LAARS Heating SystemsPage 8The combustion air can be taken through the wall, or through the roof. When taken from the wa