Service Manual Document 11019A
Service Manual for
U.H.E.
Ultra High Efciency
Water Heaters
These instructions are to be stored next to the boiler for reference purposes.
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualied in hot water boiler installation and maintenance. Improper installation and/or operation could
create carbon monoxide gas in ue gases which could cause serious injury, property damage, or death.
Improper installation and/or operation will void the warranty.
WARNING
If the information in this manual is not followed
exactly, a re or explosion may result causing
property damage, personal injury or loss of life.
Do not store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any
other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use
any phone in your building.
Immediately call your gas supplier from a
nearby phone. Follow the gas supplier's
instructions.
If you cannot reach your gas supplier, call the
re department.
Installation and service must be performed by
a qualied installer, service agency, or gas
supplier.
AVERTISSEMENT
Assurez-vous de bien suivres les instructions
données dans cette notice pour réduire au
minimum le risque d’incendie ou d’explosion
ou pour éviter tout dommage matériel, toute
blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ni
d’autres vapeurs ou liquides inammables dans
le voisinage de cet appareil ou de tout autre
appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
Ne pas tenter d’allumer d’appareils.
Ne touchez à aucun interrupteur. Ne pas
vous servir des téléphones dansle bâtiment
où vous êtes.
Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions
du fournisseur.
Si vous ne pouvez rejoindre le fournisseur
de gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés
par un installateur ou un service d’entretien
qualié ou par le fournisseur de gaz.
Troubleshooting Guide and Instructions for Service
UHE60T125E*(NA,XA)(2)
UHE60T150E*(NA,XA)(2)
UHE60T199E*(NA,XA)(2)
UHE100T150E*(NA,XA)(2)
UHE100T199E*(NA,XA)(2)
UHE100T250E*(NA,XA)(2)
UHE100T300E*(NA,XA)(2)
UHE100T399E*(NA,XA)(2)
(*) Denotes Warranty Years
Page view 0
1 2 3 4 5 6 ... 47 48

Summary of Contents

Page 1 - U.H.E

Service Manual Document 11019AService Manual for U.H.E.Ultra High Efciency Water HeatersThese instructions are to be stored next to the boiler for

Page 2 - Table of Contents

LAARS Heating SystemsPage 10Refer to ignition module illustration, is there 120VAC between P1(1) and P1(3)?Is front panel power switch light on,indi

Page 3 - Introduction

U.H.E Service ManualPage 11Determine failure mode by observing flashing LED status on ignition module.LED status and probable cause shown below.* Deno

Page 4 - Tools Required for Service

LAARS Heating SystemsPage 12Refer to ignition module illustration, Is there 24VAC between P3(7) and P3(8)?YOK, thermostat is calling for heat.Turn o

Page 5

U.H.E Service ManualPage 13°F012345678 940 26109 25400 24712 24045 23399 22771 22163 21573 21000 2044550 19906 19383 18876 18383 17905 17440 16990 165

Page 6

LAARS Heating SystemsPage 14Refer to ignition module illustration, Is there 120VAC between P1(1) and P1(3)?Refer to ignition module illustration, Is

Page 7 - Vent Tables

U.H.E Service ManualPage 15Step 5. Carefully disconnect all wires from thermostatboard.Note: it may be necessary to identify wiresfor proper re-conne

Page 8

LAARS Heating SystemsPage 16Thermostat Potentiometer Replacement ProcedureStep 4. Loosen set screw of adjustingknob (small blade screw driver)and re

Page 9

U.H.E Service ManualPage 17Thermostat Sensor (Thermistor) Replacement ProcedureStep 5. Fold back insulation just in front of burner to expose temperat

Page 10 - IGNITION MODULE

LAARS Heating SystemsPage 18Does inlet gas pressure drop more than 2" W.C. during burner ignition?Adjust gassupply regulatorInadequately sized

Page 11 - U.H.E Service Manual

U.H.E Service ManualPage 19Refer to ignition module illustration below,is there 24VAC between P3(2) and P3(5) (blue and brown wires) during the flame

Page 12 - LAARS Heating Systems

LAARS Heating SystemsPage 2Table of Contents2Page U.H.E.TMService ProcedureIntroduction 3 - - -How to use this manual 4 - - -Tool required for servi

Page 13 - APPENDIX - B

LAARS Heating SystemsPage 20Step 1. Position main power switch to “OFF”.Step 2. Disconnect (unplug) water heater from120 volt power source.Step 3. T

Page 14

U.H.E Service ManualPage 21Combustion System Replacement ProcedureStep 1. Fully inspect burner mounting insert gasket for the following:a) Tears d) Di

Page 15 - WIRING DIAGRAM

LAARS Heating SystemsPage 22Step 1. Position main power switch to “OFF”.Step 2. Disconnect (unplug) water heater from120 volt power source.Step 3. T

Page 16

U.H.E Service ManualPage 23Burner Tube InspectionStep 1. Inspect burner tube as follows (BSI ceramic fiber mesh burner, water heaters prior toserial n

Page 17 - Hot Surface Ignition Models

LAARS Heating SystemsPage 24Gas Valve Replacement ProcedureStep 6. Remove the 2 gas valve mounting screws (Torx bit) located at the11:00 O-clock &am

Page 18

U.H.E Service ManualPage 25Hot Surface Ignition Models:Are safety circuits in normal position?Does blowerenergize?Is there 120VAC across the white and

Page 19

LAARS Heating SystemsPage 26Blower Replacement ProcedureStep 5. Disconnect wire harness from blower.Step 6. Disconnect intake vent and gas supply fr

Page 20

U.H.E Service ManualPage 27Reset buttonDoes blowerenergize?NSequence of operation:The blocked vent pressure switch monitors the pressure in the exhaus

Page 21

LAARS Heating SystemsPage 28Check Exhaust Tube PressureExhaust Pressure Switch Testing and ReplacementExhaust Tubepressure tap locationExhaust tubea

Page 22 - Burner Tube Removal Procedure

U.H.E Service ManualPage 29Exhaust Pressure Switch Replacement ProcedureStep 1. Position main power switch to “OFF” position.Step 2. Loosen adhesive b

Page 23 - Burner Tube Inspection

U.H.E Service ManualPage 3IntroductionThe LAARS heating system Ultra High Efficiency Water Heater uses a low Nox premix power burner located at the to

Page 24

LAARS Heating SystemsPage 30Is igniter resistanceless than 150 Ohms (cold)?(see “check igniter resistance” below)Refer to ignition module illustrati

Page 25

U.H.E Service ManualPage 31Hot surface Igniter Replacement ProcedureStep 1. Position main power switch to “OFF”Step 2. Disconnect (unplug) water heate

Page 26 - Blower Replacement Procedure

LAARS Heating SystemsPage 32With flame sensor Disconnectedfrom ignition module, checkcontinuity to ground.Is there continuity to ground?NYFlame Sens

Page 27 - Safety Circuit Trace

U.H.E Service ManualPage 33Flame Sensor Replacement ProcedureStep 4. Fold back insulation in front of combustion assembly to expose flame sensor.(see

Page 28 - Check Exhaust Tube Pressure

LAARS Heating SystemsPage 34Ignition Module Replacement ProcedureStep 1. Position main power switch to “OFF”.Step 2. Disconnect (Unplug) water heate

Page 29

U.H.E Service ManualPage 35Transformer Replacement ProcedureStep 4. For Hot Surface Ignition models, refer to ignition module illustration below, Disc

Page 30

LAARS Heating SystemsPage 36Reset heater, observeheating cycle. Does switch open?YDoes switch open priorto 350°F?DO NOT OPERATE HEATERSystem over he

Page 31

U.H.E Service ManualPage 37Vent Safety Switch Replacement ProcedureStep 1. Position main power switch to “OFF”.Step 2. Loosen adhesive backed rubber e

Page 32

LAARS Heating SystemsPage 38Disassembly Procedure for Access to Anodes & Flue BafflesStep 1. Position main power switch to “OFF”.Step 2. Disconn

Page 33

U.H.E Service ManualPage 39Anode inspection and replacement Step 1. Turn off water supply and drain water heater.Step 2. Disassemble water heater per

Page 34

LAARS Heating SystemsPage 4Tools Required for ServiceIt is intended for this manual to be used by qualified service personal for the primary purpose

Page 35

LAARS Heating SystemsPage 40Flue baffle inspection and replacementStep 1. Disassemble heater per “Disassembly Procedure for Access to Anodes & F

Page 36

U.H.E Service ManualPage 41Powered Anode Replacement UHE100T399 models onlyPowered Anode Replacement for UHE100T399 onlyThe powered anode control modu

Page 37

LAARS Heating SystemsPage 42Collector Cover Installation ProcedureStep 1. Remove old silicone from top surface of collector flange and collector cov

Page 38

U.H.E Service ManualPage 43Product Handling - Carefully uncrate the heater. Move in place with a hand truck (Do not use the venting pipes for handles)

Page 39

LAARS Heating SystemsPage 44R44DateModel NumberSerial NumberVenting (PVC, CPVC):Intake 90's (qty)Vent size 3" or 4"Exhaust 90's

Page 40

U.H.E Service ManualPage 45Customer must specify complete model number and serial number when ordering service parts.451 Combustion Surround Assy.2 Bu

Page 41

LAARS Heating SystemsPage 46Customer must specify complete model number and serial number when ordering service parts.46AA Latch AssyBB Screw 8-32 x

Page 42

U.H.E Service ManualPage 47Customer must specify complete model number and serial number when ordering service parts.47Electronic Control ModuleScrew

Page 43 - Vent tables

LAARS Heating SystemsPage 48NOTESAC Alternating CurrentBTU/H British Thermal UnitsCO Carbon MonoxideCO2 Carbon DioxideDC Direct CurrentDSI Direct Sp

Page 44

U.H.E Service ManualPage 5UHE60T125UHE60T150UHE60T199UHE100T150UHE100T199UHE100T250UHE100T300UHE100T399125,000150,000199,999150,000199,999250,000300,0

Page 45

LAARS Heating SystemsPage 66Thermostat Sensor 11,900 Ohms @ 70°F, ECO opens @ 201°F Max., ECO close @ 100°F Min.Thermostat Board Max temp 180°F, Mi

Page 46

U.H.E Service ManualPage 7Vent TablesNotes:1) Multiply the total number of 90° elbows (intake and exhaust) by 5 feet. Do not include thetermination fi

Page 47

LAARS Heating SystemsPage 81Thermostat calls for heat.2Blower energizes, pressure switch contacts are normally closed. If the pressure switch conta

Page 48

U.H.E Service ManualPage 9Lockout conditions:The system will go into lock out mode for the following reasons:Blocked vent pressure switch contacts ope