FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualified in hot water boiler installation and maintenance. Improper installation and/or operation could
create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death.
Improper installation and/or operation will void the warranty.
Installation and Operation Instructions Document 1025Y
WARNING
If the information in this manual is not
followed exactly, a fire or explosion may
result causing property damage, personal
injury or loss of life.
Do not store or use gasoline or other
flammable vapors and liquids in the vicinity
of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not
use any phone in your building.
Immediately call your gas supplier from a
nearby phone. Follow the gas supplier's
instructions.
If you cannot reach your gas supplier, call
the fire department.
Installation and service must be performed by
a qualified installer, service agency, or gas
supplier.
AVERTISSEMENT
Assurez-vous de bien suivres les instructions
données dans cette notice pour réduire au
minimum le risque d’incendie ou d’explosion ou
pour éviter tout dommage matériel, toute
blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ni
d’autres vapeurs ou liquides inflammables dans
le voisinage de cet appareil ou de tout autre
appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
Ne pas tenter d’allumer d’appareils.
Ne touchez à aucun interrupteur. Ne pas vous
servir des téléphones dansle bâtiment où vous
vous trouvez.
Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions
du fournisseur.
Si vous ne pouvez rejoindre le fournisseur de
gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par
un installateur ou un service d’entretien qualifié ou
par le fournisseur de gaz.
Installation and Operation
Instructions for
Mini-Therm II
TM
Residential
Gas-Fired
Hydronic Boilers
Models JVS, JVT
Sizes 50-225
U.S. Patent No. 1,609,692
Canada Patent No. 383,318
Vent damper is optional in some provinces of Canada.
These instructions are to be stored in the packet
provided on the boiler.
A subsidiary of BRADFORD WHITE
Page view 0
1 2 3 4 5 6 ... 35 36

Summary of Contents

Page 1 - Mini-Therm II

MINI-THERMLAARSH0071400YFOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,qualified in hot water boile

Page 2 - TABLE OF CONTENTS

LAARS Heating SystemsPage 10SECTION 4.Gas Connections4.1 Gas Supply and PipingReview the following general instructions beforecontinuing the installat

Page 3 - General Information

Mini-Therm II Hydronic BoilerPage 11NOTE: The boiler and all other gas appliancessharing the boiler gas supply line must be firing atmaximum capacity

Page 4 - Installation Instructions

LAARS Heating SystemsPage 12A full sized, 1¼" bypass with balancing valves isstrongly recommended for all systems, and requiredwhen: 1) the boile

Page 5 - 2.2 Field Assembly

Mini-Therm II Hydronic BoilerPage 13Figure 6. Typical Plumbing Installations.JVFromSystemToSystemNON-LOW TEMPERATURE SYSTEMS(120°F+ Return Temps)Simpl

Page 6

LAARS Heating SystemsPage 14Figure 6A. Typical Plumbing Installations.KEY:PUMP CHECK VALVE VALVE ZONE VALVE UNIONAUTO AIR BLEEDERAir Scoop JVBoilerByp

Page 7 - SECTION 3

Mini-Therm II Hydronic BoilerPage 155.3 Flow RequirementsAll high recovery, low volume water boilersmust have adequate flow for efficient operation. P

Page 8 - Installation

LAARS Heating SystemsPage 165.4 Chilled Water SystemsIf the boiler is installed in conjunction withrefrigeration systems, it shall be installed so tha

Page 9

Mini-Therm II Hydronic BoilerPage 17123456BK-BLACKW-WHITER-REDY-YELLOWBL-BLUEBR-BROWNO-ORANGEP-PURPLESPARK IGNITION WIRE115V-FACTORY WIRED115V-FIELD W

Page 10 - Gas Connections

LAARS Heating SystemsPage 18Figure 9c. Wiring Diagram, Standing Pilot System (JVT).Figure 9d. Schematic, Standing Pilot System (JVT).

Page 11

Mini-Therm II Hydronic BoilerPage 19SPARKMVMV/PVPVGND24V (GR)24VTH-WMVSPARK123456789W WB BR RLO HIMVCPVHIPilot Burner WithSpark ElectrodeSensorRemote

Page 12 - Water Connections

LAARS Heating SystemsPage 2TABLE OF CONTENTSSECTION 1.General Information1.1 Introduction... 31.2 Warr

Page 13 - Mini-Therm II Hydronic Boiler

LAARS Heating SystemsPage 20Figure 10. Multiple Zone Wiring.For primary/secondary pumping: Connectto "W" in lieu of "A." Boiler re

Page 14 - LAARS Heating Systems

Mini-Therm II Hydronic BoilerPage 216.3 GroundingWARNINGThe boiler must be electrically grounded inaccordance with the requirements of the authorityha

Page 15 - 5.3 Flow Requirements

LAARS Heating SystemsPage 22On continuous pilot ignition models (JVT), if thewater temperature is below the limit setting, theignition module opens th

Page 16 - SECTION 6

Mini-Therm II Hydronic BoilerPage 23CautionShould overheating occur or the gas supply fail toshut off, do not turn off or disconnect the electricalsup

Page 17

LAARS Heating SystemsPage 2415. Replace control box cover.16. Restore power to the boiler and adjust thethermostat high enough to call for heat to ver

Page 18

Mini-Therm II Hydronic BoilerPage 25DANGERRead and understand this entire procedureprior to proceeding. Improper adjustment ofhigh altitude shutters m

Page 19

LAARS Heating SystemsPage 261. Lubricate the water circulating pump per theinstructions on the pump.2. If a strainer is employed in a pressure reducin

Page 20

Mini-Therm II Hydronic BoilerPage 27CautionTwo-stage Operating Control (JV100-225 ONLY):Factory setting is 140°F (60°C). This setting iscorrect for mo

Page 21 - Operating Instructions

LAARS Heating SystemsPage 28Table 8. Troubleshooting Guide.# Symptom Cause Remedy1. Pump not A. No power A. Check circuit breakers and power source.op

Page 22 - 7.2 Start-up

Mini-Therm II Hydronic BoilerPage 299.3 Troubleshooting Honeywell S8600 Intermittent Pilot SystemSome boilers may be equipped with an ignition module

Page 23 - Figure 12. Gas Valves

Mini-Therm II Hydronic BoilerPage 3SECTION 1.General Information1.1 IntroductionThis manual provides information necessary forthe installation, operat

Page 24 - Air Shutter Adjustment

LAARS Heating SystemsPage 309.4 Electrical Troubleshooting1. Remove the control box cover on the front of theboiler.2. Verify that 115V is reaching th

Page 25 - Maintenance

Mini-Therm II Hydronic BoilerPage 31Heat Distribution UnitsTransfers heat from the water supplied by the boiler tothe area to be heated through the us

Page 26 - Operation

LAARS Heating SystemsPage 32Description Model, Size JVS-50 JVT-50 JVS-75 JVT-75 JVS-100 JVT-100 JVS-125 JVT-125 JVS-160 JVT-160 JVS-225 JVT-225Pilot G

Page 27 - Troubleshooting

Mini-Therm II Hydronic BoilerPage 33Description Model, Size JVS-50 JVT-50 JVS-75 JVT-75 JVS-100 JVT-100 JVS-125 JVT-125 JVS-160 JVT-160 JVS-225 JVT-22

Page 28 - 9.2 Troubleshooting Guide

LAARS Heating SystemsPage 34Figure 15. Parts Identification.11.3Exploded ViewVent DamperDraft DiverterTopRear PanelBurner with Pilot BracketPilot Asse

Page 29

Mini-Therm II Hydronic BoilerPage 35

Page 30 - Glossary

H0071400YA subsidiary of BRADFORD WHITE Corporation800.900.9276 • Fax 800.559.1583 (Customer Service, Service Advisors)20 Industrial Way, Rochester, N

Page 31 - Replacement Parts

LAARS Heating SystemsPage 41. Plumbing materials for the bypass piping, whichis required for:a. Any system where the return watertemperature may be le

Page 32

Mini-Therm II Hydronic BoilerPage 52.2 Field Assembly1. Mini-Therm II boilers have built-in draft diverterfor natural draft operation.2. Find the vent

Page 33

LAARS Heating SystemsPage 6CautionDo not force motor operation when operator isfastened to the damper by moving the damperblade, turning the shaft or

Page 34 - 11.3Exploded View

Mini-Therm II Hydronic BoilerPage 7SECTION 3.Venting3.1 Combustion Air SupplyThe boiler location must provide sufficientair supply for proper combusti

Page 35

LAARS Heating SystemsPage 8WARNINGVent pipe diameter must be as required by theNational fuel Gas Code Z223.1 or the CanadianInstallation Codes for Gas

Page 36 - H0071400Y

Mini-Therm II Hydronic BoilerPage 9WARNINGOperation of appliances with a blocked commonvent may lead to serious injury or death. Safetydevices must be