Installation, Operation and Maintenance Instructions Document 2060D
H2090800D
Installation,
Operation and
Maintenance
Instructions for
Mighty Max
Hydronic Boilers
Model HH
Sizes 320M - 1000M
WARNING
If the information in this manual is not
followed exactly, a fire or explosion may
result causing property damage, personal
injury or loss of life.
Do not store or use gasoline or other
flammable vapors and liquids in the vicinity
of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not
use any phone in your building.
Immediately call your gas supplier from a
nearby phone. Follow the gas supplier's
instructions.
If you cannot reach your gas supplier, call
the fire department.
Installation and service must be performed by a
qualified installer, service agency, or gas
supplier.
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualified in hot water boiler installation and maintenance. Improper installation and/or operation could
create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death.
Improper installation and/or operation will void the warranty.
AVERTISSEMENT
Assurez-vous de bien suivres les instructions
données dans cette notice pour réduire au
minimum le risque d’incendie ou d’explosion ou
pour éviter tout dommage matériel, toute
blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ni
d’autres vapeurs ou liquides inflammables dans
le voisinage de cet appareil ou de tout autre
appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
Ne pas tenter d’allumer d’appareils.
Ne touchez à aucun interrupteur. Ne pas vous
servir des téléphones dansle bâtiment où vous
vous trouvez.
Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions
du fournisseur.
Si vous ne pouvez rejoindre le fournisseur de
gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par
un installateur ou un service d’entretien qualifié ou
par le fournisseur de gaz.
Page view 0
1 2 3 4 5 6 ... 31 32

Summary of Contents

Page 1 - Mighty Max

Installation, Operation and Maintenance Instructions Document 2060DH2090800DInstallation,Operation andMaintenanceInstructions forMighty MaxHydronic Bo

Page 2 - TABLE OF CONTENTS

Page 10LAARS HEATING SYSTEMS3. Provide a boiler installed above radiation levelwith a low water cutoff device either as part ofthe boiler or at the ti

Page 3 - General Information

Mighty Max Hydronic BoilerPage 11Category IVertical Ventingwith DuctedCombustion AirHorizontal VentingAny Vent Which Does Not MeetCategory I Combustio

Page 4 - Installation Instructions

Page 12LAARS HEATING SYSTEMS3. Remove the vent collar/stack from the fluecollector. Do not damage the vent collar/stackduring removal.4. Remove the bl

Page 5

Mighty Max Hydronic BoilerPage 13HeaterSizePipe Diameter Max Pipe LengthMax No.of ElbowsSide WallVent TerminalPart NumberSide WallCombustion AirTermin

Page 6 - 2F. Gas Supply and Piping

Page 14LAARS HEATING SYSTEMS2L-4. Side Wall Vent TerminalThe side wall vent hood must be used when theheater is vented through a side wall. It provide

Page 7

Mighty Max Hydronic BoilerPage 152M-1. Air From RoomStandard requirements for providing air forcombustion and ventilation are provided by ANSIZ223.1/N

Page 8 - 2G. Water System Requirements

Page 16LAARS HEATING SYSTEMS1. Remove the louvered plate from the left side ofthe boiler.2. Remove the adapter plate from the shippingcontainer.3. Ins

Page 9

Mighty Max Hydronic BoilerPage 17Figure 12. Wiring Diagram.IGNITION SYSTEM 20 ON/OFFSIZES 320-1000, NATURAL OR PROPANECautionLabel all wires prior to

Page 10 - Information

Page 18LAARS HEATING SYSTEMSpre-ignition purge, while the fan clears thecombustion chamber, the igniter is turnedon. The igniter takes about 25 second

Page 11 - Non-Category I

Mighty Max Hydronic BoilerPage 19Use a single, inclined manometer or digitalmanometer with a 4.0 inch water column range. Installshutoff valves at the

Page 12

Page 2LAARS HEATING SYSTEMSTABLE OF CONTENTSSECTION 1.General Information1A. Introduction ... 31B. Wa

Page 13 - 2L. Venting

Page 20LAARS HEATING SYSTEMSCautionThis appliance is equipped with an ignitiondevice which automatically lights the burner.Do not try to light the bur

Page 14

Mighty Max Hydronic BoilerPage 21The difference in pressure between the venturiinlet tap and the gas plenum tap (see Figure 16). Thismeasurement is ta

Page 15 - Mighty Max Hydronic Boiler

Page 22LAARS HEATING SYSTEMSBy setting the gas offset pressure and gas orificedifferential pressure according to Table 11, the correctinput rate and g

Page 16 - SECTION 3

Mighty Max Hydronic BoilerPage 23inner surface of the heat exchanger tubes andrestrict the water flow. Inspect the heat exchanger inaccordance with Se

Page 17 - IGNITION SYSTEM 20 ON/OFF

Page 24LAARS HEATING SYSTEMSOther maintenance requirements include:1. Periodic cleaning of filters, when supplied.2. Lubrication of moving parts (when

Page 18 - 3B. Hi-Limit Checkout

Mighty Max Hydronic BoilerPage 25Figure 20. Troubleshooting Chart.

Page 19 - 3D. To Start Up System

Page 26LAARS HEATING SYSTEMSFigure 21. Lower Front Panel Removal.5B. Venturi and Gas Pressure RegulatorSystem5B-1. Field CheckoutSee Section 3B “Ventu

Page 20 - 3E. To Shut Down System

Mighty Max Hydronic BoilerPage 27SECTION 6Parts List for Mighty Max HH Boiler6A. General InformationTo order or purchase parts for the Laars MightyMax

Page 21

Page 28LAARS HEATING SYSTEMSFront ViewRight Side View36108952071213113621141538412

Page 22 - Maintenance

Mighty Max Hydronic BoilerPage 29Front ViewRear ViewRight Side ViewLeft Side View3132173023262728 2537253316183529193439

Page 23 - 4C. Gas and Electric Controls

Mighty Max Hydronic BoilerPage 3Some accessory items are shipped in separatepackages. Inspect everything for damage immediatelyupon delivery, and advi

Page 24 - Troubleshooting

Page 30LAARS HEATING SYSTEMSItem Description Part Number16. Cover, Machined In/Out ... 2015020017. Plate, Mach. Adapter3

Page 25

Mighty Max Hydronic BoilerPage 31

Page 26 - 5C. Electrical Components

H2090800DWaterpik Technologies, Inc.6000 Condor Drive, Moorpark, CA 93021 • 805.529.2000 • FAX 805.529.593420 Industrial Way, Rochester, NH 03867 • 60

Page 27 - SECTION 6

Page 4LAARS HEATING SYSTEMSSECTION 2.Installation Instructions2A. General InformationInstall the Mighty Max HH boiler in accordancewith the procedures

Page 28

Mighty Max Hydronic BoilerPage 5not require the full freeze protection of a 50%/50%mixture, it is beneficial to use a maximum 30% glycolsolution. This

Page 29 - Right Side ViewLeft Side View

Page 6LAARS HEATING SYSTEMSoperate at high altitudes have appropriatestickers or tags attached.3. The figures in Table 3 should be used to size thegas

Page 30

Mighty Max Hydronic BoilerPage 7Figure 4. T-Fitting Sediment Trap Installation.Gas SupplyInletTeeFitting3 In.(76mm) Min.CapNippleTo EquipmentInletSIZE

Page 31

Page 8LAARS HEATING SYSTEMS2G. Water System Requirements2G-1. Flow RequirementsThe Model HH boilers must have continuousflow through the heat exchange

Page 32 - Waterpik Technologies, Inc

Mighty Max Hydronic BoilerPage 92G-3. System Pressure RequirementsThe Model HH boilers are designed to operateon closed, pressurized systems. Maintain